SERIES
700
MAXIMUM
RELIABILITY MECHANICAL LEVEL SWITCHES
Download the
Delta Controls Series 700 Summary Datasheet
Note: You will need the Acrobat Reader to view the data sheet.
|
SUMMARY
OF MODELS AND STYLES
TOP
INSERTED FLOAT ACTUATED LEVEL
SWITCHES
Operation:
A float is carried up and down by variations in liquid level or interface
position.
One or more switch actions occur at selected level positions.
|
|
|
|
Delta Controls
Model 709
Alarm
- Uses:
Provide high or low level alarm or interface position
- Insertion:
Up to 10 feet (3m) below the flange face
- Switch
Action: Single point
- Specific
Gravity: From 0.35 to 2.40 SGU
- Temperature:
From 150 to 750°F (-100 to +400° C)
- Pressure:
From 15 to 1200 PSIG (-1 to +80 BAR)
- Process
Connection: 1" to 4" NPT threaded; 1" to 12"
flanged, up to 900# rating; ASA, DIN or JIS equivalent
|
|
|
|
Delta Controls
Multiswitch Models 710
and 711
- Uses:
Provide high and / or low level alarm, pump control, etc.
- Insertion:
Up to 10 feet below the flange face
- Switch
Action: From 1 to 4 points of alarm and/or differential; up to 60"
differential available with Type 711
- Specific
Gravity: From 0.35 to 2.40 SGU
- Temperature:
From 150 to 750°F (-100 to +400° C)
- Pressure:
From 15 to 1200 PSIG (-1 to +80 BAR)
- Process
Connection: 1" to 4" NPT threaded; 1" to 12"
flanged, up to 900# rating; ASA, DIN or JIS equivalents
|
TOP
INSERTED DISPLACER ACTUATED
LEVEL SWITCHES
Operation:
The weight of a displacer is supported by a spring. Variations in liquid
level cause the displacer to move up and down. Switching action occurs
as the level passes each displacer.
|
|
|
|
Delta Controls
Model 715 Alarm
- Uses:
High or low alarm for liquid level or interface position
- Insertion
and Switching band: up to 50 feet (15m) maximum
- Switch
action: Single point alarm
- Specific
Gravity: form 0.25 to 2.4 SGU
- Temperature
from 20 to 500°F (-30 to +260°
C)
- Pressure:
from 15 to 2200 PSIG (-1 to +155 BAR)
- Process
Connection: 2" to 4" NPT threaded; 2" to 12"
flanged up to 1500# rating; ASA, DIN, or JIS equivalents
|
|
|
|
Delta Controls
Model 716, 717, 718 Multiswitch
- Uses:
High and/or low alarm; single and multiple pump control
- Insertion
and Switching band: up to 50 feet (16 m) maximum
- Switch
action: From 1 to 4 points of alarm and/or on-off pump control
- Specific
Gravity: form 0.25 to 2.4 SGU
- Temperature
from 20 to 500°F (-30 to +260° C)
- Pressure:
from 15 to 2200 PSIG (-1 to +155 BAR)
- Process
Connection: 3" to 4" NPT threaded; 3" to 12"
flanged up to 1500# rating; ASA, DIN, or JIS
style
|
SIDE
INSERTED FLOAT OR DISPLACER ACTUATED LEVEL SWITCHES
Operation:
A solid displacer or heavy-duty float is supported by a pivot shaft
and counterweight. Single point alarm switching action occurs as the
liquid level or interface position crosses the center line of the body.
Uses: High and low alarm for level, interface position, and sequencing
|
|
|
|
Delta Controls
Model 735 Alarm
NPT Process Connection
- Insertion:
14 inches basic
- Specific
Gravity: 0.6 to 2.4
- Temperature:
-85 to 1000°F (-60 to +540° C)
- Pressure:
15 to 2250 PSIG (-1 to +155 BAR)
- Process
Connection:1" to 3" threaded, 1 ½" to 4" flanged,
up to 900# rating, ASA, DIN, JIS
|
|
|
|
Delta Controls
Model 735 Alarm
Flanged Process Connection
- Insertion:
12 to 24 inches
- Specific
Gravity: 0.15 to 2.4
- Temperature:
-85 to 1000°F (-60 to +540° C)
- Pressure:
15 to 3600 PSIG (-1 to +250 BAR)
- Process
Connection: 2" to 12" flanged, up to 1500# rating, ASA,
DIN, JIS, any facing
|
|
|
|
Delta Controls
Model 740 Two Point Alarm or Differential Pump Control
- Operation:
A pivoted float rides on the liquid level or interface position. Two
switch actions occur as the elevation varies.
- Uses:
Two point alarm or on-off pump control
- Specific
Gravity: 0.4 to 2.4
- Temperature:
-50 to 750°F (-47 to +400° C)
- Pressure:
-15 to 750 PSIG (-1 to +50 BAR)
- Process
Connection: 3" NPT threaded, 3" to 12" flanged, up
to 600# rating, ASA, DIN, JIS
|
|
EXTERNAL
CAGE FLOAT OR DISPLACER ACTUATED LEVEL SWITCHES
|
|
|
|
Delta Controls
Model 750
Float or Displacer
Level or Interface Alarm
- Operation:
The weight of a displacer or heavy-duty float is supported by a counterweight
and a pivot shaft. Switching occurs as the level (interface) crosses
the body centerline.
- Specific
Gravity: 0.23 to 2.4
- Temperature:
-200 to 1100°F (-130 to +650° C)
- Pressure:
15 to 6000 PSIG (-1 to +410 BAR)
- Process
Connection: Top/Bottom or other
½", ¾", or 1" NPT or Socket Weld
½" to 2" flanged, 600#, ANSI
½" to 1" flanged, 1500#, ANSI
½" to 2" hubs, 10,000#, Greyloc
|
|
|
|
Delta Controls
Model 760
and 762 Alarm with Vertically Rising Element
- Operation:
A float or displacer moves up and down as the liquid level (interface)
varies. Switch action occurs at a preset elevation
- Switching:
Single alarm
- Specific
Gravity: 0.35 to 2.4
- Temperature:
-100 to 800°F (-70 to +430° C)
- Pressure:
15 to 20,000 PSIG (-1 to 1400 BAR)
- Process
Connection:
SB or SSB style
½", ¾", or 1" NPT, stub, or S. W.
½" to 2" flanged, to 2500#, ANSI
2" Greyloc clamp hubs
|
|
Model
765
Model
767
Model
770
|
|
Delta Controls
Model 765, 767, and 770
Differential Control or Multiswitch
- Operation:
A float with a long stroke action moves up and down as the liquid level
varies. Switching occurs at up to four separate points.
- Switching
Stations: 1 to 4; alarm and/or differential
- Differential:
up to 72"
- Specific
Gravity: 0.4 to 2.4
- Temperature:
-20 to 750°F (-30 to +400° C)
- Pressure:
-15 to 2200 PSIG (-1 to +155 BAR)
- Process
Connection: Same as type 760
|
|
HIGH
TEMPERATURE AND PRESSURE LEVEL SWITCH
|
|
|
|
Delta Controls
Model 763 With Displacer Element
- Operation:
A counterweighted horizontal pivoting element operates an output switch
as the liquid level or interface crosses the body centerline.
- Uses:
Steam drums, condensate trap drains, Dowtherm®, etc.
- Switch
Action: Single point alarm
- Specific
Gravity: 0.3 to 2.4 units
- Interface
Differential: 0.1 unit minimum
- Temperature:
-350 to 1100°F (-200 to +600° C)
- Pressure:
-15 to 6000 PSIG (-1 to +415 BAR)
- Process
Connection: 1", 1 ½", or 2" butt, stub, or socket
weld; ANSI flanges or Greyloc hub
|
|
|
|
Contact
Delta Controls
|
|
|
 |